operations:procedures:loss_of_pressure

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
operations:procedures:loss_of_pressure [2026/07/14 19:57] zeagleoperations:procedures:loss_of_pressure [2026/07/14 20:29] (current) zeagle
Line 2: Line 2:
 In the event that the system is no longer pressurized, the [[components:valves:blowoff:division_two_blowoff]] needs to be opened to allow air to escape the system and to avoid stresses on the system. In the event that the system is no longer pressurized, the [[components:valves:blowoff:division_two_blowoff]] needs to be opened to allow air to escape the system and to avoid stresses on the system.
  
 +<WRAP center round important 60%>
 If the booster pumps are off for an extended period of time (for maintenance, power outage, etc...) and the [[components:gauges:mains_pressure_gauge]] reads 0 or close to 0, it is critical that the [[components:valves:blowoff:division_two_blowoff]] be opened before the booster pumps are restarted. If the booster pumps are off for an extended period of time (for maintenance, power outage, etc...) and the [[components:gauges:mains_pressure_gauge]] reads 0 or close to 0, it is critical that the [[components:valves:blowoff:division_two_blowoff]] be opened before the booster pumps are restarted.
 +</WRAP>
 +
  
   - Ensure both [[components:pumps:booster_pump_left|]] and [[components:pumps:booster_pump_right|]] are turned off at the [[components:controls:control_box|]]   - Ensure both [[components:pumps:booster_pump_left|]] and [[components:pumps:booster_pump_right|]] are turned off at the [[components:controls:control_box|]]
-  - Ensure that the all [[components:valves:main_shutoff|]] are open+  - Ensure that the all [[components:valves:main_shutoff|]] valves are open
   - Open the [[components:valves:blowoff:division_two_blowoff]]   - Open the [[components:valves:blowoff:division_two_blowoff]]
   - Put one of the booster pumps into manual mode   - Put one of the booster pumps into manual mode
   - Let the booster pump run for at least 10 minutes, the water coming out of the blowoff should be steady, no sputtering or air.   - Let the booster pump run for at least 10 minutes, the water coming out of the blowoff should be steady, no sputtering or air.
   - The [[components:gauges:mains_pressure_gauge]] should show some pressure now.   - The [[components:gauges:mains_pressure_gauge]] should show some pressure now.
-  - Slowly close [[components:valves:main_shutoff:division_two_shutoff]]+  - Slowly close [[components:valves:blowoff:division_two_blowoff|]]
   - Set the booster pumps to auto   - Set the booster pumps to auto
   - Monitor the [[components:gauges:mains_pressure_gauge|]] and the pressure gauge in the control box. It should return to 20 psi   - Monitor the [[components:gauges:mains_pressure_gauge|]] and the pressure gauge in the control box. It should return to 20 psi
   - The booster pump set to auto should automatically shut off when the system reaches ~22 psi   - The booster pump set to auto should automatically shut off when the system reaches ~22 psi