 ====== Loss of Pressure ====== ====== Loss of Pressure ======
-In the event that the system is no longer pressurized, the [[components:valves:division_two_blowoff]] needs to be opened to allow air to escape the system and to avoid stresses on the system.+In the event that the system is no longer pressurized, the [[components:valves:blowoff:division_two_blowoff]] needs to be opened to allow air to escape the system and to avoid stresses on the system. 
 + 
 +<WRAP center round important 60%> 
 +If the booster pumps are off for an extended period of time (for maintenance, power outage, etc...) and the [[components:gauges:mains_pressure_gauge]] reads 0 or close to 0, it is critical that the [[components:valves:blowoff:division_two_blowoff]] be opened before the booster pumps are restarted. 
 +</WRAP>
  
-If the booster pumps are off for an extended period of time (for maintenance, power outage, etc...) and the [[component:gauge:mains_pressure_gauge]] reads 0 or close to 0, it is critical that the [[components:valves:division_two_blowoff]] be opened before the booster pumps are restarted. 
  
   - Ensure both [[components:pumps:booster_pump_left|]] and [[components:pumps:booster_pump_right|]] are turned off at the [[components:controls:control_box|]]   - Ensure both [[components:pumps:booster_pump_left|]] and [[components:pumps:booster_pump_right|]] are turned off at the [[components:controls:control_box|]]
-  - Ensure that the [[components:valves:division_two_shutoff]] is open +  - Ensure that the all [[components:valves:main_shutoff|]] valves are open 
-  - Open the [[components:valves:division_two_blowoff]]+  - Open the [[components:valves:blowoff:division_two_blowoff]]
   - Put one of the booster pumps into manual mode   - Put one of the booster pumps into manual mode
   - Let the booster pump run for at least 10 minutes, the water coming out of the blowoff should be steady, no sputtering or air.   - Let the booster pump run for at least 10 minutes, the water coming out of the blowoff should be steady, no sputtering or air.
-  - The [[components:gauge:mains_pressure_gauge]] should show some pressure now. +  - The [[components:gauges:mains_pressure_gauge]] should show some pressure now. 
-  - Slowly close [[components:valves:division_two_shutoff]] +  - Slowly close [[components:valves:blowoff:division_two_blowoff|]] 
-  - Set the booster pump to auto +  - Set the booster pumps to auto 
-  - Monitor the [[components:gauges:mains_pressure_gauge]] and the pressure gauge in the control box. It should return to 20 psi+  - Monitor the [[components:gauges:mains_pressure_gauge|]] and the pressure gauge in the control box. It should return to 20 psi
   - The booster pump set to auto should automatically shut off when the system reaches ~22 psi   - The booster pump set to auto should automatically shut off when the system reaches ~22 psi